  • Equipment Type
  • Thermal Mass Flow Sensor
  • Resolution
  • 0.001 Nm/h
  • Port Size
  • 1/2 (DN 15), 1 (DN 25), 2 (DN 50), and other sizes available
  • Temperature
  • Medium: -30C to +110C; Ambient: 0C to +50C
  • Mounting Type
  • Insertion type
  • Display Type
  • Backlit LCD, graphical display
  • Operating Voltage
  • 1836 V DC
  • Features
  • Bidirectional measurement, easy installation, IP65 protected, menu operation via touch buttons
  • Power Supply
  • 1836 V DC
  • Gas Pressure
  • Max. 16 bar (depending on sensor variant)
  • Automation Grade
  • Automatic
  • Response Time
  • t90 < 1s
  • Measuring Range
  • 0.25 to 825 Nm/h depending on probe and pipe diameter
  • Accuracy
  • 1.5% of m.v. 0.3% of f.s.
  • Interface Type
  • 420 mA output, Modbus RTU, pulse output, optional relay
  • Application
  • Measurement of compressed air and technical gases
  • Humidity
  • 095% RH (non-condensing)
  • Usage
  • Inline or insertion flow measurement in pipes/ducts
  • Machine Weight
  • Approx. 0.5 kg (sensor only)
  • Control Mode
  • Digital/Analog Output control
  • Cable Length
  • Up to 10 m (depending on version)
  • Media Compatibility
  • Compressed air, nitrogen, oxygen, argon, CO2, other non-corrosive gases
  • Sensor Material
  • Stainless Steel 1.4301 (probe), others on request
  • Protection Class
  • IP65
  • Mounting Accessories
  • Welding socket, positioning adapter, ball valve for sensor removal under pressure
  • Comm. Options
  • Optional RS485, Modbus RTU
  • Electrical Connection
  • M12, 5-pin, A-coded
  • Display Functions
  • Flow, totalizer, temperature
  • Operation
  • Menu driven, multilingual
  • Calibration
  • Five-point factory calibration certificate included
  • Pressure Loss
  • Negligible due to no moving parts
  • Process Connection
  • 1/2" ball valve for hot tap (optional)
  • Data Storage
  • EEPROM, retentive for configuration and counter values
  • Probe Lengths
  • 120/160/220/300/400 mm
 
 

About VA 500 - Flow sensor for compressed air and gases

 Special features of flow sensor VA 500:

  • RS 485 interface, Modbus-RTU as a standard
  • Option integrated display for m/h and m
  • Usable from 1/2 to 12 (DN 300)
  • Easy installation under pressure
  • 4...20 mA analogue output for m/h resp. m/min
  • Pulse output for m
  • Inner diameter adjustable via keypad
  • Consumption counter resettable
  • Adjustable values at the display of the flow sensor: Reference conditions, C and mbar, 4...20 mA scaling, pulse weight


Robust and Flexible Measurement Solutions

The VA 500 flow sensor is engineered with stainless steel for durability and reliability, making it ideal for industrial environments. Compatible with a range of gases and supplied with a five-point calibration certificate, it ensures accurate measurements across different media and conditions.


User-Friendly Operation and Installation

Featuring a large backlit LCD display and multilingual, menu-driven controls, the VA 500 simplifies on-site operation. Its insertion-type design, optional hot tap ball valve, and range of probe lengths enable straightforward installation and sensor maintenanceeven under pressure.


Advanced Output and Communication Capabilities

The sensor supports multiple output and communication options, including analog (420 mA), digital, Modbus RTU, and pulse signals, ensuring seamless integration with diverse automation and monitoring systems. Configuration and data retention are supported by robust EEPROM storage.

FAQs of VA 500 - Flow sensor for compressed air and gases:


Q: How do I install the VA 500 flow sensor into existing compressed air or gas pipelines?

A: The VA 500 is designed for insertion mounting and can be installed quickly using a welding socket or positioning adapter. For installations where shutting down the process is not possible, the optional 1/2" ball valve enables safe hot tap sensor insertion and removal under pressure.

Q: What gases can the VA 500 accurately measure, and are there material compatibility concerns?

A: This flow sensor reliably measures compressed air, nitrogen, oxygen, argon, CO2, and other non-corrosive gases. Its probe is made from stainless steel 1.4301, suitable for these media. For special or corrosive gases, alternative materials may be available on request.

Q: When should the VA 500 be used for gas flow measurement?

A: The VA 500 is ideal when precise measurement of gas or compressed air flow and consumption is required, such as in energy monitoring, leak detection, and process optimization within industrial settings. Its broad measuring range, high accuracy, and five-point calibration ensure dependable results.

Q: Where can the VA 500 be installed within an industrial environment?

A: This sensor can be installed in pipes or ducts handling compatible gases, in line or as an insertion device. With probe lengths from 120 to 400 mm and port sizes from 1/2" to 2" (and others), it adapts to a variety of pipeline diameters commonly found in factories and processing plants.

Q: What operational benefits does the VA 500 provide compared to traditional flow meters?

A: With its non-moving parts, the VA 500 offers negligible pressure loss, reducing energy waste. Its digital outputs, fast response time (t90 < 1 s), accurate bidirectional measurements, and menu operation simplify integration and maintenance, while its protective IP65-rated housing supports use in harsh industrial environments.

Q: How does the VA 500 handle configuration and long-term data integrity?

A: All configuration and counter values are securely stored in EEPROM memory, ensuring settings and measurements are retained even in the event of power loss. This supports reliable, uninterrupted data tracking for process monitoring and control.

Tell us about your requirement
product

Price:

Quantity
Select Unit

  • 50
  • 100
  • 200
  • 250
  • 500
  • 1000+
Additional detail
Mobile number

Email

More Products in Flow Meter Category

Chart Recorder

Chart Recorder

Application : Industrial Data Logging

Usage : Recording process parameters

Features : Longterm Data Recording

Power Supply : 230 V AC, 50 Hz

Mounting Type : Panel Mounted

Interface Type : Analog Outputs

VA 525 - Compact in-line flow sensor

VA 525 - Compact in-line flow sensor

Application : For compressed air and noncorrosive gases

Usage : Flow measurement in compressed air systems

Features : Bidirectional measurement, compact design, easy installation, maintenancefree

Power Supply : 24 V DC 10%

Mounting Type : Inline, directly into pipe system

Interface Type : Analog output (420 mA), Pulse, Modbus RTU/RS485 (optional)

VA 570 - Flow meter with integrated measuring section

VA 570 - Flow meter with integrated measuring section

Application : Measurement and monitoring of compressed air and noncorrosive gases

Usage : Industrial, process control, energy management

Features : Integrated measuring section, rugged industrial design, easy installation, no moving parts, low pressure loss, maintenancefree

Power Supply : 24 V DC (1830 V DC)

Mounting Type : Inline mounting with integrated measuring section

Interface Type : 420 mA, pulse, RS485/Modbus

Digital Process Meter

Digital Process Meter

Application : Measuring and indicating process signals

Usage : Industrial process measurement

Features : High brightness LED, Multirange input, Overrange indication, Compact design

Power Supply : 230V AC, 50/60Hz

Mounting Type : Panel Mount

Interface Type : Panel Mount Screw Terminals



Back to top